Multiple Earthing System
Points : multiple earthing system
A TN-C-S system is as the TN-S but the supply cable sheath is also the neutral, i.e. it forms a
combined earth/neutral conductor known as a PEN (protective earthed neutral) conductor.
The installation earth and neutral are separate conductors.
Showing posts with label Protective Devices. Show all posts
Showing posts with label Protective Devices. Show all posts
Sunday, 3 May 2015
Earth Resistance Value
Earth Resistance Value
Points : earth resistance value, what are the factors on which earth resistance value depends? how earth resistance can be reduced?
Earth resistance value depends upon:
a) Condition of Soil.
b) Moisture of the soil
c) Temperature of the soil.
d) Depth of the electrode at which it is embedded.
e) Size and spacing of earth electrodes.
a) Condition of Soil.
b) Moisture of the soil
c) Temperature of the soil.
d) Depth of the electrode at which it is embedded.
e) Size and spacing of earth electrodes.
Thursday, 30 April 2015
What Points are To Be Connected To Earth?
What Points are To Be Connected To Earth?
Points : what points are to be connected to earth?
The following equipment should be connected to earthing through earth wire as per Electricity Rules.
i) The neutral conductor of 3 phases. 4 wire a.c. electrical system and the middle conductor of two phase, 3 wire system should be earthed by not less than two separate and distinct connections with earth at the generating station and at the sub-station.
i) The neutral conductor of 3 phases. 4 wire a.c. electrical system and the middle conductor of two phase, 3 wire system should be earthed by not less than two separate and distinct connections with earth at the generating station and at the sub-station.
Functions of Earthing
Functions of Earthing
Points : Functions of Earthing
Earthing may be defined as the process of connecting the non-current carrying parts of
electrical apparatus to the general mass of the earth in such a manner that at all times an
immediate discharge of electrical energy place without any danger.
Specifications of Earth Wire and Earth Plate
Specifications of Earth Wire and Earth Plate
Points : specifications of earth wire and earth plate,
(i) Specifications of Copper Earth Plate: 60 cm x 60 cm x 3mm high conductivity copper plate
fitted with copper lug. bolt, nut and washer. The finished plate shall have reasonably clean and
smooth surface, free from scratches. porosity, black oxide and any other defect.
Wednesday, 29 April 2015
Material Required For GI Pipe Earthing
Material Required For GI Pipe Earthing
Points : material required for gi pipe earthing
The list of material with complete specifications for GI pipe earthing is given below
Determination of Size of Earth Wire And Earth Plate for Domestic And Motor Installations
Determination of Size of Earth Wire And Earth Plate for Domestic And Motor Installations
Points : determination of size of earth wire and earth plate for domestic and motor installations
In case of I w voltage supply, the consumer need not provide his own earthing system, with an
independent electrode as the supplier is required to provide and maintain a suitable earthed
terminal in an accessible position at or near the point of commencement of supply at the
consumer premises. Hence earth plate is not-required on submain distribution boads for
connecting each terminal provided on submain distribution boards to the earthing terminal
provided by the supplier on main distribution board.
Earth Continuity Conductor
Earth Continuity Conductor
Points : earth continuity conductor
This is the part of the earthing system which joins or bonds together all the metal parts of an installation: Conduit, ducts, boxes, metal casing of switches, switchfuses, fuse distribution boards,
Installation with High Resistance of Earth
Installation with High Resistance of Earth
Points : installation with high resistance of earth
Danger now exists on the exposed metalwork because the fault current of 4.2 amps flow through a
resistance of 50 ohms in the install the metalwork and earth. The first indication that a fault
has occurred is when someone earth. The first indication that a fault has occurred is when
someone touches the metal work and gets a severe or possibly fatal shock.
Friday, 24 April 2015
Points To Remember While Providing Earthing
Points To Remember While Providing Earthing
Points : points to remember while providing earthing
Following point should be remembered while providing earthing to an installation and premises.
Various details given as per I.S. specification are:
(i) Distance
The distance of the electrode from the installation at the premises should be more than 1.5
meter.
Monday, 20 April 2015
Selection of Fuse Wire
Selection of Fuse Wire
Points : selection of fuse wire, Cable and Fuse Ratings for Motors
The fuse rating for steady load circuits such as heating loads should be equal to or next
greater than the rating of smallest cable in the circuit. For fluctuating load circuits like
those of motor, capacitor and transformer loads fuse should have such current-time
characteristic as to allow the short time over current to flow without blowing. For this it is
sometimes necessary to select fuses of rated current greater than that of the cable of the
circuit, In motor circuit fuse is to be rated for short circuit and not for over current
protection which is looked after by over current protection provided in starter.
Comparison of HRC Fuse and Circuit Breakers
Comparison of HRC Fuse and Circuit Breakers
Points : comparison of hrc fuse and circuit breakers
(i) HRC fuse possess higher rupturing capacity compared to Circuit breakers in the medium
voltage range. Fuses with rupturing capacity of 75 MVA (breaking current app. 100 KA) arc
available Breakers with corresponding capacity will be too bulky.
(ii) HRC fuses are cheaper than the circuit breakers.
(iii) HRC fuse take less space and are simpler to install and maintain.
(ii) HRC fuses are cheaper than the circuit breakers.
(iii) HRC fuse take less space and are simpler to install and maintain.