Selection of Fuse Wire
Selection of Fuse Wire
Points : selection of fuse wire, Cable and Fuse Ratings for Motors
The fuse rating for steady load circuits such as heating loads should be equal to or next
greater than the rating of smallest cable in the circuit. For fluctuating load circuits like
those of motor, capacitor and transformer loads fuse should have such current-time
characteristic as to allow the short time over current to flow without blowing. For this it is
sometimes necessary to select fuses of rated current greater than that of the cable of the
circuit, In motor circuit fuse is to be rated for short circuit and not for over current
protection which is looked after by over current protection provided in starter. The over
current protection, on the other hand, is not suitable for clearing heavy short circuit current.
As very heavy starting current over long period and such these are rated at twice the full load
current of motor. If this were not so fuses would operate every time the motor is started up.
With three phase motors it is always desirable to be liberal in selecting the size of the fuse
rather than allowing one of the fuses to operate causing motor to run on single phase and get
damaged for good for motors which have protracted starting period or are driving heavy inertia
loads it may be necessary to select fuses of required current-time characteristics.
For other type of fluctuating load circuits such as capacitor circuit, fluorescent lighting
circuit, battery charger circuit and transformer circuit, the fuses should, as a general guide,
have 50% are rated current.
Note
1. If one fuse feeding a three phase motor has operated, it is a good practice to replace all
the unblown fuses also otherwise there may be single phasing trouble. For the same very reason
all the three fuses should always be of same rating.
2. Fuses are inserted in live wires only and not in neutral wire.
Cable and Fuse Ratings for Motors
These are given in Table below:
No comments:
Post a Comment