(i) open-circuit
(ii) high resistance of load circuit
(iii) faulty contact between brushes and commutator and
(iv) commutator surface dirty or greasy. 4. In case of shunt wound generator (a) the resistance of the shunt field circuit may be greater than the critical resistance;
(b) the resistance in the load circuit may be lower than the critical resistance;
(c) the speed of rotation may not be equal to rated one. Remedy In case the generator is started up for the first time, it may be that no voltage will be built up either because the poles have no residual magnetism or the poles have retained some residual magnetism but the field winding connections are reversed so that the magnetism developed by the field winding on start has destroyed the residual magnetism and the machine can not “build up”. In both the cases, the field coils must be connected to a dc source (a storage battery) for a short while to magnetise the poles. The application of external source of direct current to the field is called flashing of the field.