Range Extension of D.C & A.C Instruments - Multiple Choice Questions and Answers
Points : range extension of d.c & a.c instruments mcqs, objective type question, multiple choice questions and answer
1. For extending the range of d.c. meters, we use....
(a) Shunt
(b) Multiplier
(c) Both (a) & (b)
(d) C.T. & P.T.
2. The voltage drops across shunt and basic meter are...
(a) Different
(b) Same
(c) Maximum
(d) Minimum
Showing posts with label Range Extension of D.C & A.C Instruments. Show all posts
Showing posts with label Range Extension of D.C & A.C Instruments. Show all posts
Tuesday, 13 January 2015
Circuit Diagram of Loaded Current Transformer and Potential Transformer
Circuit Diagram of Loaded Current Transformer and Potential Transformer
Points : Circuit Diagram of Loaded Current Transformer and Potential Transformer
Shows C.T. and PT. connected with the load to measure load current, potential & the current coil of
wattmeter is connected through C.T. and standard 5°A ammeter. The potential coil of wattmeter is connected
with P.T. and standard 110 V voltmeter.
Characteristics of Potential Transformer
Characteristics of Potential Transformer
Points : Characteristics of Potential Transformer
(i) Effect of secondary current or VA
If we increase the secondary burden, the secondary current is increased, and therefore, the primary current
increase. Both primary and secondary voltage drops increase and thus for a given value of V, the value of V
decreases and hence the actual ratio increases as the burden increases. The ratio error increase becoming
more negative with increase in burden. This variation of ratio error is almost linear with change in
burden.
With regard to phase angle, the voltage VP is more advanced in phase because of increased voltage drops with increase in secondary burden. The phasor Vs reversed is retarded in phase due to increase in secondary voltage drops. Thus with increase in burden, the phase angle between VP and V reversed increases, becoming more negative.
With regard to phase angle, the voltage VP is more advanced in phase because of increased voltage drops with increase in secondary burden. The phasor Vs reversed is retarded in phase due to increase in secondary voltage drops. Thus with increase in burden, the phase angle between VP and V reversed increases, becoming more negative.
Characteristics of Current Transformer
Characteristics of Current Transformer
Points : Characteristics of Current Transformer, Effect of P.F. of Secondary Burden on Errors, Effective of change of primary current, Effect of change in secondary burden, Effect of change of frequency,
(1) Effect of P.F. of Secondary Burden on Errors
a. Ratio Error
It is observed that for all inductive burdens the secondary current. Is lags behind the
secondary induced voltage, Es so that is +ve. Under these conditions the actual transformation
ratio is always greater than the turns ratio. For burdens which are sufficiently capacitive, I loads E and
so is -ve. under these conditions the actual transformation ratio decreases becoming less than the turns
ratio for values of “6” approaching -900.
Theory of Potential Transformer
Theory of Potential Transformer
Points : theory of potential transformer
The general theory of potential transformer is similar to that for power transformers, except that, as the
current in the burden is very small, the total primary current is not much greater than the “no-load”
current. The voltage drops due to the resistance and leakage reactance of the windings are of great
importance, as an accurate value ratio is required. The phasor diagram of PT.
Monday, 12 January 2015
Potential Transformer
Potential Transformer
Points : Potential Transformer, Definition
These transformers are extremely accurate ratio step-down transformers and are used in conjunction with
standard low-range voltmeters (100-12-V) whose deflection when divided by transformation ratio gives the
true voltage on the primary or high-voltage side.
Current Transformer Methods of Reduction of Errors
Current Transformer Methods of Reduction of Errors
Points : Current Transformer Methods of Reduction of Errors
The errors of C.T can be eliminated b the methods already explained. Also there are some design features
which help us to minimize the errors. They are listed below:
(1) By designing the C.T. a low flux density.
(2) By using the core of high permeability material.
(1) By designing the C.T. a low flux density.
(2) By using the core of high permeability material.
Theory of Current Transformer
Theory of Current Transformer
Points : Theory of Current Transformer
For satisfactory and accurate performance it is necessary that the ratio of transformer of the instrument
transformer should he constant within close limits however, in practice, it is found that neither current
transformation ratio Ii/I2 (in case of current transformers) nor voltage
transformation ratio V/V2 (in case of potential transformers) remains constant.