Electric Service Connections / Service Line
Points : Electric Service Connections / Service Line,
Service Line:
Power is transmitted from generating station or substation to the place of public utility by means of transmission
lines and there from power is further distributed by means of distributors or distributing lines. The consumers
are supplied with power by taking connections (tappings) from distributing lines use of cables (surface or
underground) and some times overhead lines when distance of consumer’s premises from the nearest distribution line
support exceeds 45 meters) is made.
The overhead line or cable connecting the supplier’s distributor Line to the consumer’s is called the service
line. The service connection terminates at the point, where they supply conductors enter the meter. As mentioned
above, for service line either use of overhead line or of underground cable can be made so the service lines arc
of two types namely (i) Overhead and (ii) Underground service lines. Overhead service line is further sub-divided
on the basis of the wires coming through the conduits or with the help of a service entrance cable. For overhead
service connection by bare conductor use of all aluminum stranded conductor (A A C), A C S R conductor or hard
drawn copper (now-a-days rarely used because of higher cost) of different sizes is made according to the load of
the consumer. For copper conductor minimum size used in 10 SWG provided the load does not exceed 1 kw.
Use of 8 SWG copper conductor or 13.9 mm2 A A C or A C S R is made for connecting domestic and
commercial premises provided the load does not exceed 2.5 kw (light and fan load) and 2.5 kW in case of power. For
connecting power load upto 12 kW use of 6 SWG copper conductor or 19.4 mm2 A A C or A C S R is made. The weather
proof or P V C cables of aluminium core (rarely of copper core) are used for cable service connection 3”2 core I
trapdoor cable is used for underground service connections.