Determination of Size of Earth Wire And Earth Plate for Domestic And Motor Installations
Points : determination of size of earth wire and earth plate for domestic and motor installations
In case of I w voltage supply, the consumer need not provide his own earthing system, with an
independent electrode as the supplier is required to provide and maintain a suitable earthed
terminal in an accessible position at or near the point of commencement of supply at the
consumer premises. Hence earth plate is not-required on submain distribution boads for
connecting each terminal provided on submain distribution boards to the earthing terminal
provided by the supplier on main distribution board.
From submain distribution boards copper no 14 SWG wire will be required to run to three-pin
socket outlets and connected to their earth sleeve.
In case of motor installations consumer is to provide his own earthing system. The size of earth
wire and earth plate used will depend upon the rating of the motor for which it is to be used.
The conductor used for earthing purpose should not be of: cross-section less than that of 14
SWG, and greater than 64.5 mm2 from mechanical consideration. From electrical consideration the
copper earth wire should not be of size lesser than current carrying conductor. GI wire may also
be used as earth wire provided its conductivity is not lesser than that of copper conductor. The
figures regarding size of earth wire for various capacity motors for guidance are given in Table.